TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
February, 2010
PREACTION SPRINKLER
SYSTEM
With the Model G-2000, G-3000, or G-4000 Valve: When the detector operates, the solenoid valve
opens (Figure 10d). Prime water is drained from the prime chamber, causing the G series valve to
open, filling the sprinkler piping with water. Water from the intermediate chamber of the G series valve
pressurizes the sensing end of the PORV, causing the PORV to open, which continually vents
prime water pressure (Figure 10d).
Figure 10d: Single Interlock System with Electric Release System using a Model G Series Valve